Ring Generator - Switch Settings
When replacing a NT6D42CB or NT6D42CC Ring Generator, always check the DIP switch settings!
SW1: Freq. |
1 | 20Hz * |
2 | 25Hz |
3 | 50Hz |
* North America: 20Hz/86V
SW2: Ring Voltage |
1-2-3 Off | 86V * |
1 On, 2-3 Off | 80V |
2 On, 1-3 Off | 75V |
3 On, 1-2 Off | 70V |
SW2: Msg Volts |
4 Off | 100V * |
4 On | 150V |
- Set Ring Frequency with SW1 (position 1)
- Set Ring and Message Waiting Voltage with SW2 (all off)
Recommended options:
Application | Ringing frequency | Ringing voltage | Message Waiting voltage | Ringing output |
North America | 20 Hz | 86 Vac | P5: High voltage | Low impedance |
British Telecom | 25 Hz | 80 Vac | P4: No High voltage | Low impedance |
Settings in detail:
High voltage message waiting | Pin location |
Disable | Jumper in P4 |
Enable | Jumper in P5 |
Ringing output | Jumper location J7 |
Low impedance (normal) | Connect pins 1 and 2 |
High impedance (Australia) | Connect pins 2 and 3 |
Ringing frequency (Hz) | Position SW1 |
20 | 1 |
25 | 2 |
50 | 3 |
NT6D42CB | SW2 |
Ringing voltage | Message waiting voltage | 1 | 2 | 3 | 4 |
86 Vac | -120 Vdc | off | off | off | off |
86 Vac | -150 Vdc | off | off | off | on |
80 Vac | -120 Vdc | on | off | off | off |
80 Vac | -150 Vdc | on | off | off | on |
75 Vac | -120 Vdc | off | on | off | off |
75 Vac | -150 Vdc | off | on | off | on |
70 Vac | -120 Vdc | off | off | on | off |
70 Vac | -150 Vdc | off | off | on | on |
NT6D42CC | SW2 |
Ringing voltage | Message waiting voltage | 1 | 2 | 3 | 4 |
86 Vac | -100 Vdc | off | off | off | off |
86 Vac | -150 Vdc | off | off | off | on |
80 Vac | -100 Vdc | on | off | off | off |
80 Vac | -150 Vdc | on | off | off | on |
75 Vac | -100 Vdc | off | on | off | off |
75 Vac | -150 Vdc | off | on | off | on |
70 Vac | -100 Vdc | off | off | on | off |
70 Vac | -150 Vdc | off | off | on | on |